Powerbolt · 20 ft container

Up to 6.25 MWh in a 20 ft container.

DC block with liquid-cooled racks, BMS, HVAC and fire suppression built in. Plug & play with minimal civil works, ready for transport and connection to the PCS: the unit we use to build multi-MWh plants.

6,058 × 2,438 × 2,896 mm · 20 ft

5.015MWh
Energy per container

@ 0.5C · also 3.34 and 6.25 MWh

95%
DC round-trip efficiency

96% @ 0.25P

1,123–1,498Vdc
DC block voltage

12 racks 1P416S

≤ 46t
Weight

20HC · 6,058 × 2,438 × 2,896 mm

Inside

4,992 cells, twelve racks, one block.

In the 5.015 MWh Powerbolt, each rack strings 416 LFP cells of 314 Ah up to 1,331 V nominal. Twelve racks in parallel add up to 5.015 MWh with 95% DC efficiency at 0.5P.

Closed 5 MWh battery container with a technician in front
5.015 MWh block, closed and ready for shipping.
Liquid-cooled battery racks inside a 5 MWh container
1P416S racks with 314 Ah LFP cells.
Open 5 MWh container with the battery racks accessible from the front
Front-accessible racks for maintenance.
Configuration
1P416S × 12
Current per rack
157 A discharge · 193 A charge (5 min)
Associated PCS
6 × 417 kW or 2 × 1.25 MW
Communication
CAN · Ethernet

BK integration

From DC block to operating plant

The container is the energy block. Around it we integrate power conversion, medium voltage, plant control and operation. A single party accountable for the plant meeting the grid operator's requirements.

  • Integrated
  • In the project
  • Optional
  1. 01

    314 Ah LFP cells

    4,992 cells in 12 racks of 416 in series (5.015 MWh). 8,000 cycles to 70% state of health (0.5P, 25 ± 2 °C). The 6.25 MWh model uses 587 Ah cells.

    Integrated
  2. 02

    Rack-level and system BMS

    Monitoring of every cell, balancing and protection of every rack. Class B functional safety.

    Integrated
  3. 03

    Liquid cooling and HVAC

    Liquid circuit per pack with ΔT ≤ 2 °C, thermal and acoustic insulation and self-contained container HVAC.

    Integrated
  4. 04

    Detection and suppression

    Aerosol fire suppression built into the container (3.34 and 5.015 MWh); three-level protection, pack, cluster and container, on the 6.25 MWh model.

    Integrated
  5. 05

    PCS and transformer station

    Six 417 kW PCS or two 1.25 MW PCS per container, plus whatever medium-voltage transformer the point of connection requires.

    In the project
  6. 06

    BK EMS, PPC and SCADA

    EMS Max for utility scale: forecasting, arbitrage, balancing services and system operator setpoints. PPC for power control at the point of connection.

    In the project
  7. 07

    Plant communications

    CAN and Ethernet in the block to the plant controller. IEC 61850 and Modbus at EMS level.

    Integrated

Models and datasheet

Three models, one 20 ft container.

3.34 MWh for smaller points of connection, 5.015 MWh as the standard block and 6.25 MWh with a 587 Ah cell for maximum density. Data from the 2026 catalogue datasheet.

Powerbolt 5.015 MWh, BK EnergiesLiquid cooling

Powerbolt 5.015 MWh

Published datasheet
5.015MWh
Energy @ 0.5C
95%
DC RTE @ 0.5P
12racks
1P416S · 314 Ah
  • GB/T 36276
  • IEC 62619
  • IEC 63056
  • IEC 62477
  • IEC 61000
  • IEC 62933-5-2
  • UN 38.3

Full datasheet · Powerbolt

Powerbolt specifications
ParameterPowerbolt 3.34 MWhPowerbolt 5.015 MWhPowerbolt 6.25 MWh
System
Rated energy3,343.97 kWh5.015 MWh @ 0.5C6,251 kWh
Power (0.5P) / associated PCS1,672 kW2,500 kW (PCS: 6 × 417 kW or 2 × 1.25 MW)On request
DC voltage1,123.2–1,497.6 V1,123.2–1,497.6 V1,331.2 V rated
DC efficiency (RTE)—96% @ 0.25P · 95% @ 0.5POn request
Battery
CellLFP 3.2 V · 314 AhLFP 3.2 V · 314 AhLFP 587 Ah
Configuration—1P416S × 12 racks1P416S × 8 racks
Max. discharge / charge current—157 A × 12 / 193 A × 12 (5 min)On request
Service life8,000 cycles (0.5P, 25 ± 2 °C, 70% SOH)8,000 cycles (0.5P, 25 ± 2 °C, 70% SOH)On request
Environment
Operating temperature−20…50 °C−20…50 °COn request
Ingress protection ratingIP55IP55 (IP67 pack)IP54 (customisable)
Anti-corrosionC4C4C5
CoolingLiquidLiquidLiquid
Control
Fire suppressionAerosolAerosolThree levels: pack, cluster and container
CommunicationCAN · EthernetCAN · EthernetOn request
Functional safety—Class B—
Mechanical
Dimensions (W × D × H)6,058 × 2,438 × 2,896 mm6,058 × 2,438 × 2,896 mm (20HC)6,058 × 2,438 × 2,896 mm
Weight≤ 35 t≤ 46 t≈ 50 t

20 ft liquid-cooled container (catalogue, p. 18). Certifications: 3.34 MWh GB/T 36276 and UN 38.3; 5.015 MWh GB/T 36276, IEC 62619, IEC 63056, IEC 62477, IEC 61000, IEC 62933-5-2 and UN 38.3; 6.25 MWh on request. Indicative parameters, subject to final design.

Indicative sizing

How many Powerbolts does your plant need?

Move the target energy. We calculate with 5.015 MWh containers at 0.5C; the actual design depends on the point of connection, the duration and the expected degradation.

5 MWh190 MWh
4
5.015 MWh containers
10 MW
Power at 0.5C (2 h)
59 m²
Container footprint (excluding aisles)
24
417 kW PCS (or 8 × 1.25 MW)

Simplified calculation without degradation margins or auxiliary services. Our largest system delivered: 188 MWh in Lianyungang (China).

Applications

Built for MWh-scale plants

The Powerbolt is the building block when energy is measured in megawatt hours.

Safety and certifications

Contain any incident within the container.

Integrated fire suppression, sealed packs and self-contained HVAC. Every level of the system has its own barrier.

  • 01

    Layered protection

    IP55 container with IP67 packs (5.015 MWh); customisable IP54 on the 6.25 MWh model. C4 or C5 anti-corrosion.

  • 02

    Aerosol fire suppression

    Integrated aerosol fire suppression; on the 6.25 MWh model, three-level protection: pack, cluster and container.

  • 03

    Climate-controlled

    Thermal and acoustic insulation and self-contained HVAC: the cells stay within their temperature window all year round.

  • 04

    Functional safety

    Class B on the 5.015 MWh Powerbolt, with centralised control. Operation from −20 to 50 °C.

Technical compartment of a Powerbolt with electrical panel and fire suppression cylinder
Technical compartment: control panel, protection devices and fire suppression system.

Standards declared in the datasheet

  • GB/T 36276

    Lithium batteries for energy storage (China)

  • IEC 62619

    Industrial lithium battery safety

  • IEC 63056

    Safety of lithium batteries for energy storage

  • IEC 62477

    Safety of power converters

  • IEC 61000

    Electromagnetic compatibility

  • IEC 62933-5-2

    Safety of electrochemical energy storage systems

  • UN 38.3

    Transport of lithium batteries

Certifications for the 5.015 MWh Powerbolt as stated in the datasheet (catalogue, p. 18). The 3.34 MWh model declares GB/T 36276 and UN 38.3; those for the 6.25 MWh model are available on request.