Cabinets · DC cabinet
241, 261 or 418 kWh in an outdoor cabinet.
Liquid-cooled LFP battery cabinets without an inverter: they connect to the project's PCS with no risk of circulating currents or short circuits between clusters. For sites where a container won't fit.
- 241–418kWh
- Three cabinet sizes
- 768–1,331Vdc
- Rated voltage
- 314Ah
- 3.2 V LFP cell
- IP55
- Outdoor installation
BK241 · BK261 · BK418
Match your PCS window
0.5C · DOD 100%
Liquid cooling · ΔT < 2 °C
Architecture
More cells in series, more energy and more voltage.
All three cabinets use 3.2 V, 314 Ah LFP cells. From the BK241 to the BK418 they go from 240 to 416 cells in series, so energy and voltage rise together: from 768 to 1,331.2 Vdc nominal.
So size is chosen on two criteria: the energy you need and the inverter's DC voltage window. For more energy, use several cabinets in parallel. If you want the inverter built into the same unit, see Power Pro.
BK integration
What's inside a Cabinet
The Cabinet is the energy side of the system. We supply the rest: inverter, protection, control and operation, sized for your point of connection.
- Integrated
- In the project
- Optional
- 01Integrated
3.2 V LFP cells · 314 Ah
From 240 to 416 cells in series. 0.5C and 100% rated depth of discharge.
- 02Integrated
BMS
Monitoring of every cell and every pack, with early detection of imbalances.
- 03Integrated
Liquid cooling
Core temperature difference below 2 °C. Pump included; system auxiliary consumption ≤ 4,000 W (220 Vac).
- 04Integrated
DC protection
Protection on each cluster for series connection to the PCS with no circulating currents or short circuits between clusters.
- 05In the project
PCS
Bidirectional inverter selected for DC voltage and power. We integrate it into the project.
- 06In the project
Detection and suppression
Sized to the site risk assessment. The cabinet passes the UL 9540A test at unit level.
- 07In the project
BK EMS
EMS Core or Pro: self-consumption, peak shaving, arbitrage and backup, with 24/7 monitoring.
BK241–BK418 datasheet
Three sizes, all the data.
Select a size or click its column header. Data from the 2026 catalogue datasheet.
Liquid coolingBK241
Published datasheet- 241kWh
- Rated energy
- 768Vdc
- Rated voltage
- 1P240S
- Configuration
- IEC 62619
- IEC 62933
- IEC 61000
- UL 1973
- UL 9540A
Liquid coolingBK261
Published datasheet- 261.25kWh
- Rated energy
- 832Vdc
- Rated voltage
- 1P260S
- Configuration
- IEC 62619
- IEC 62933
- IEC 61000
- UL 1973
- UL 9540A
Liquid coolingBK418
Published datasheet- 418kWh
- Rated energy
- 1,331.2Vdc
- Rated voltage
- 3,930kg
- Weight
- IEC 62619
- IEC 62933
- IEC 61000
- UL 1973
- UL 9540A
Full datasheet · DC Cabinets BK241 · BK261 · BK418
Scroll the table sideways if you can't see every model
| Parameter | BK241 | BK261 | BK418 |
|---|---|---|---|
| Battery | |||
| Rated energy | 241 kWh | 261.25 kWh | 418.00 kWh |
| Configuration | 1P240S | 1P260S | 1P416S |
| Rated voltage | 768 Vdc | 832.0 Vdc | 1,331.2 Vdc |
| Voltage range | 648–864 V | 676–936 V | 1,081.6–1,497.6 V |
| Rated current (0.5C) | 157 A | 157 A | 157 A |
| Max. current (5 min) | 193 A | 193 A | 193 A |
| Depth of discharge | 100 % | 100 % | 100 % |
| Mechanical and environmental | |||
| Dimensions (D × W × H) | On request | On request | 1,300 × 1,300 × 2,373.5 mm |
| Weight | On request | On request | 3,930 kg |
| Protection | IP55 | IP55 | IP55 |
| Cooling | Liquid | Liquid | Liquid |
| Altitude | ≤ 2,000 m | ≤ 2,000 m (up to 4,500 m on request) | ≤ 2,000 m (up to 4,500 m on request) |
Common to the series (catalogue, p. 10): 3.2 V · 314 Ah LFP cell, core ΔT < 2 °C, IP55 outdoor, passes UL 9540A at unit level. System auxiliary consumption ≤ 4,000 W including pump (220 Vac). Charge and discharge temperature for guaranteed service life: 25 ± 5 °C. Certifications: IEC 62619, IEC 62933, IEC 61000, UL 1973 and UL 9540A.
Applications
Where a Cabinet fits
Where you need more energy than an all-in-one and less space than a container.
Industry and C&I
Industrial estates and factories: several cabinets next to the transformer substation, with no container civil works.
PV + BESS hybridisation
Small and mid-sized solar PV plants looking to shift output to high-price hours.
Uninterrupted backup (STS)
Data centres and commercial premises with critical loads and little plant-room space.
Safety and certifications
Safe at unit level.
The Cabinet passes the UL 9540A test at unit level, which assesses whether thermal runaway in one cell spreads to the rest of the cabinet.
- 01
UL 9540A at unit level
Test passed: thermal runaway in one cell does not spread through the cabinet.
- 02
No circulating currents
Series connection to the PCS with no risk of circulating current or short circuits between clusters.
- 03
Uniform temperature
Liquid cooling with less than 2 °C core temperature difference: less degradation, longer life.
- 04
IP55 outdoor
IP55 outdoor cabinet with liquid cooling, up to 2,000 m altitude (BK261 and BK418: up to 4,500 m on request).

Standards declared in the datasheet
UL 9540A
Thermal runaway propagation test
UL 1973
Batteries for stationary use
IEC 62619
Industrial lithium battery safety
IEC 62933
Grid-connected energy storage systems
IEC 61000
Electromagnetic compatibility
Certifications declared in the Cabinets datasheet (catalogue, p. 10).