LiqRack · liquid cooling
+20%service life vs air cooling
High-voltage rack with liquid-cooled packs in parallel.
- ΔT between cells ≤ 2 °C
- IP67 at pack level
- Operation from −40 to 60 °C
- Class B functional safety
Racks · LiqRack · AirRack
Packs in series with rack BMS, protection and communications: from 172.8 to 372.7 kWh per rack, with liquid or air cooling. The foundation on which we build Powerbolt containers.
Four configurations
900–1,500 Vdc
Compared with air cooling
0.5C on the rest
From cell to container
Each level adds voltage, thermal management and protection. You can buy the rack from us as a DC block or the complete system.
1.005 kWh
3.2 V · 314 Ah
× 52 in series →
52.25 kWh
166.4 V · liquid cooling
× 8 in series →
418 kWh
1,331.2 V nominal
× 12 per container →
5.015 MWh
1,123.2–1,497.6 Vdc · 20 ft
String used in the BK261 and BK418 Cabinets and the 5.015 MWh Powerbolt (314 Ah cell). With a 280 Ah cell, the same architecture gives the 372.7 kWh LiqRack.
BK integration
A cell on its own is not a product. Every pack and every rack ships with its own management, cooling and protection, ready to connect to the PCS and the EMS.
Incoming inspection of every cell before assembly, with serial-number traceability for every pack and every rack.
Monitoring of every pack and rack-level control. Class B functional safety.
Liquid-cooled packs in parallel with ΔT ≤ 2 °C between cells, or parallel air cooling.
Rack electrical protection built in as standard.
To connect the rack to the plant's EMS and SCADA.
When the rack goes into a Powerbolt, we add the inverter, fire suppression and enclosure HVAC.
Optional for projects integrating other equipment: EMS Core, Pro or Max depending on scale.
Racks
Two liquid-cooled LiqRacks and two air-cooled AirRacks, all with an operating range of 900 to 1,500 Vdc. Data from the 2026 catalogue datasheets.
Liquid cooling
Liquid cooling
Air cooling
Air coolingFull datasheet · Racks
Scroll the table sideways if you can't see every model
| Parameter | LiqRack 280Ah 1P416S | LiqRack 280Ah 1P384S | AirRack 280Ah 1P416S | AirRack 150Ah 1P360S |
|---|---|---|---|---|
| Cell | LFP 280 Ah | LFP 280 Ah | LFP 280 Ah | LFP 150 Ah |
| Configuration | 1P416S | 1P384S | 1P416S | 1P360S |
| Pack | 8 × LiqPack 1P52S | 8 × LiqPack 1P48S | AirPack 1P16S | AirPack 1P24S |
| Rated energy | 372.7 kWh | 344 kWh | 372.7 kWh | 172.8 kWh |
| Rated voltage | 1,331.2 V | 1,228.8 V | 1,331.2 V | 1,152 V |
| Operating range | 900–1,500 Vdc | 900–1,500 Vdc | 900–1,500 Vdc | 900–1,500 Vdc |
| Charge/discharge rate | 0.5C | 0.5C | 0.5C | 1C |
| Cooling | Parallel liquid cooling | Parallel liquid cooling | Parallel air cooling | Parallel air cooling |
| Dimensions (W × D × H) | 860 × 1,153 × 2,333 mm | 860 × 1,068 × 2,333 mm | 1,142 × 835 × 2,418 mm | 960 × 788 × 2,341 mm |
| Weight | ≈ 3,200 kg | ≈ 3,000 kg | ≈ 3,200 kg | ≈ 1,700 kg |
| Functional safety | Class B | Class B | Class B | Class B |
| Certifications | IEC 62619 · IEC 61000 · UL 1642 · UL 1973 | GB/T 36276 · IEC 62619 · IEC 61000 · UL 1642 · UL 1973 | GB/T 36276 | IEC 62619 · IEC 61000 |
LiqRack: liquid-cooled packs in parallel, +20% service life compared with air cooling, ΔT between cells ≤ 2 °C, IP67 at pack level and operation from −40 to 60 °C (catalogue, p. 6). AirRack: modular design and up to 1C discharge on the 150 Ah version (catalogue, p. 7). Indicative parameters, subject to final design.
Packs
Cells, BMS and protection in one module. Packs are supplied integrated into their rack.

Liquid cooling, IP67.
8 per LiqRack 1P416S

Liquid cooling, IP67.
8 per LiqRack 1P384S

Air cooling, 280 Ah cell.
AirRack 280Ah 1P416S

Air cooling, 150 Ah cell.
AirRack 150Ah 1P360S
Thermal management
+20%service life vs air cooling
High-voltage rack with liquid-cooled packs in parallel.
1Cmax. discharge (AirRack 150 Ah)
Rack with parallel air cooling: a simpler, more cost-effective architecture.
Applications
Integrators, equipment manufacturers and projects that need a bespoke DC block.
Safety and certifications
System safety starts with the chemistry, the pack and the testing. These are the barriers and the standards declared in each datasheet.
All racks, with a rack BMS that trips on any deviation.
LiqPacks are IP67 and operate with ΔT ≤ 2 °C between cells.
Serial number for every pack, rack and system, with a quality dossier.
100% of units pass FAT before leaving the factory.

Standards declared in the datasheet
IEC 62619
Industrial lithium battery safety
IEC 61000
Electromagnetic compatibility
UL 1642
Lithium cell safety
UL 1973
Batteries for stationary use
GB/T 36276
Lithium batteries for energy storage (China)
Each rack has its own list of certifications in the datasheet (catalogue, pp. 6–7).

Inspection, welding, BMS, assembly and testing. Every pack goes through the same checks before it ships.
Tell us the voltage, the energy and the PCS you work with. We will send you datasheets, certificates and lead times.