Skip to content

Power Pro · All-in-one

The entire battery system in one cabinet.

LFP cells, power conversion, BMS, EMS, air conditioning and fire suppression integrated and tested in one outdoor cabinet. From 112 to 522 kWh and from 50 to 250 kW.

1,000 × 1,350 × 2,300 mm · BK241 · BK261
1,900 × 1,350 × 2,300 mm · BK522

112–522kWh
Energy per cabinet

Five models

50–250kW
Rated AC power

400 Vac three-phase

8,000cycles
Service life

0.5P, 25 ± 2 °C, down to 70% SOH

IP54–55
Outdoor installation

Up to 55 °C ambient and 2,000 m

The range

Five sizes, one architecture.

The hybrid BK112H, with PV input and island mode, for medium loads and off-grid systems. From BK241 to BK522 with liquid cooling for industry and EV charging. All run at 0.5P: around two hours of autonomy at rated power.

  • A single connection

    400 V three-phase AC output with neutral. No shelter, container or integration works needed: it connects to the switchboard and is configured.

  • Modular growth

    The modular architecture lets you match capacity and power to the project and expand later with more units in parallel.

  • Operator-ready

    RS485, Ethernet and CAN depending on model. Integrates with SCADA, PPC and our EMS without third-party gateways.

Liquid-cooled BK Energies Power Pro
Power Pro · BK241 to BK522

On site and in the factory

Power Pro in operation, not in a catalogue.

Real installations in industry and off-grid systems, and units on the integration line before shipping to site.

BK integration

What goes inside a Power Pro

We don't resell boxes. We select every component, integrate it, test it and commission it with our own EMS. A single point of responsibility for the complete system.

  • Integrated
  • In the project
  • Optional
  1. 01

    314 Ah LFP cells

    Lithium iron phosphate chemistry: cobalt-free, thermally stable and rated for 8,000 cycles down to 70% state of health (0.5P, 25 ± 2 °C).

    Integrated
  2. 02

    BMS and BMU

    Monitors the voltage and temperature of every cell, balances the system and trips on any deviation.

    Integrated
  3. 03

    Bidirectional PCS

    400 Vac three-phase, power factor adjustable from −1 to +1, THDi ≤ 3% and 100% unbalanced load. PCS with up to 98% efficiency. On the BK112H, hybrid inverter with PV input and island mode in under 20 ms.

    Integrated
  4. 04

    Liquid or air cooling

    Closed-loop liquid cooling (BK241–BK522) or forced ventilation (BK112H).

    Integrated
  5. 05

    Detection and suppression

    Detection integrated into the BMS and aerosol fire suppression on all models.

    Integrated
  6. 06

    BK EMS

    Self-consumption, peak shaving, arbitrage and backup with demand forecasting. 24/7 monitoring and predictive maintenance.

    Integrated
  7. 07

    Communications

    RS485 and Ethernet on all models; CAN on BK112H, BK289 and BK522; Modbus TCP on the BK289.

    Integrated

Models and datasheets

Choose the size. Get the full datasheet.

Select a model to see its key figures; the table highlights its column. Data from the BK Energies technical catalogue.

BK241, BK EnergiesLiquid cooling

BK241

Published datasheet
241kWh
Rated energy
125kW
Rated power
137.5kW
Maximum AC power

Compact 1 × 1.35 m footprint: around two hours of autonomy at rated power.

  • GB/T 34120
  • GB/T 36276
  • IEC 62477
  • IEC 62619
  • IEC 61000

Full datasheet · Power Pro All-in-One

Power Pro All-in-One specifications
ParameterBK112HBK241BK261BK289BK522
Battery
CellLFP 3.2 V · 314 AhLFP 3.2 V · 314 AhLFP 3.2 V · 314 AhLFP 3.2 V · 314 AhLFP 3.2 V · 314 Ah
Configuration1P112S1P240S1P260S—2P260S
Rated energy112.53 kWh241 kWh261 kWh289 kWh522.5 kWh (25 °C, 0.5P)
DC range / rated voltage302.4–403.2 V / 358.4 V648–864 V702–936 V / 832 V720–1,000 V / 921.6 V702–936 V / 832 V
Service life8,000 cycles (0.5P, 25 ± 2 °C, 70% SOH)8,000 cycles (0.5P, 25 ± 2 °C, 70% SOH)8,000 cycles (0.5P, 25 ± 2 °C, 70% SOH)≥ 8,000 cycles (70% capacity) · 0.5P8,000 cycles (0.5P, 25 ± 2 °C, 70% SOH)
PV input
Max. PV input power100 kW————
Max. voltage · MPPT range / rated1,000 V · 180–850 V / 600 V————
Start-up · number of MPPTs200 V · 2————
Max. input / short-circuit current6 × 45 A / 6 × 55 A————
AC side
Rated power50 kW125 kW125 kW125 kW250 kW
Maximum power / overload—137.5 kW137.5 kW1.2 Pn for 1 min1.1× continuous · 1.2× for 1 min
Rated voltage400 V (340–436 V) · 3P+N+PE400 Vac · 340–440 V (−15% … +10%)400 Vac · 340–440 V (−15% … +10%)400 Vac · 300–460 V400 V (−15% … +15%) · 3P+N+PE
Current79.8 A max. output182 A rated182 A rated182 A rated360 A rated
Frequency50/60 Hz (45–55 / 55–65 Hz)50/60 Hz ± 2.5 Hz50/60 Hz ± 2.5 Hz50/60 Hz50/60 Hz (45–55 / 55–65 Hz)
Power factor · THDi—−1 … +1 · ≤ 3 %−1 … +1 · ≤ 3 %−1 … +1 · ≤ 3 %−1 … +1 · ≤ 3 %
Isolated output (THDu) · unbalanced load—< 3% with linear load · 100%< 3% with linear load · 100%< 3% with linear load · 100%< 3% with linear load · 100%
Island modeYes · switchover < 20 ms————
System
Efficiency> 86% system> 88% system · PCS 98% max.> 88% system · PCS 98% max.> 89% max.≥ 88% system
CoolingAirLiquidLiquidLiquidLiquid
Fire suppressionAerosolAerosolAerosolAerosolAerosol
CommunicationRS485 · Ethernet · CANRS485 · EthernetRS485 · EthernetRS485 · CAN · Modbus TCPEthernet · CAN · RS485
Noise—< 75 dB< 75 dB< 75 dB< 75 dB
Environment
Ingress protection rating—IP54 (IP67 pack)IP54 (IP67 pack)IP55IP55
Ambient temperature−20…55 °C−30…55 °C−30…55 °C−30…55 °C (derates above 45 °C)−30…55 °C
Humidity / max. altitude≤ 95% RH non-condensing · 2,000 m≤ 95% RH non-condensing · 2,000 m≤ 95% RH non-condensing · 2,000 m0–95% non-condensing · —≤ 95% RH non-condensing · 2,000 m
Mechanical
Dimensions1,355 × 1,300 × 2,300 mm1,000 × 1,350 × 2,300 mm1,000 × 1,350 × 2,300 mm1,588 × 1,380 × 2,450 mm1,900 × 1,350 × 2,300 mm
Weight1,500 kg2,450 kg2,670 kg3,050 kg5,340 kg

Indicative parameters, subject to final factory design and configuration (catalogue, pp. 12–16). Certifications per model in each datasheet. "—": figure not published in the datasheet.

Applications

Where a Power Pro works

A cabinet that arrives integrated and tested. It fits where the site and the space dictate.

Safety and certifications

Detect, isolate, suppress.

Safety starts with LFP chemistry and continues through every layer of the cabinet. Four barriers before a fault can leave the cell.

  • 01

    LFP chemistry

    Lithium iron phosphate contains no cobalt and is one of the most thermally stable chemistries.

  • 02

    Early detection

    Combustible gas, smoke and temperature sensors connected to the BMS and EMS.

  • 03

    Aerosol fire suppression

    Aerosol fire suppression system integrated into the cabinet, on all models.

  • 04

    Sealed pack

    IP67 packs inside an IP54 or IP55 cabinet, depending on model, for outdoor installation.

Inside a 215 kWh cabinet with the battery packs, BMS and wiring in view
Inside a 215 kWh cabinet during integration: packs, BMS and protection panel.

Standards declared in the datasheet

  • IEC 62619

    Industrial lithium battery safety

  • IEC 62477

    Safety of power converters

  • IEC 62933

    Grid-connected energy storage systems

  • IEC 63056

    Safety of lithium batteries for energy storage

  • IEC 61000

    Electromagnetic compatibility

  • UN 38.3

    Transport of lithium batteries

Standards declared in the Power Pro datasheets (catalogue, pp. 12–16); each model has its own list in the datasheet above.

Which Power Pro does your installation need?

Send us your load curve or your bill and we will tell you the model, the power and the expected savings.